synced JUST NOW
01 Record

CVE-2022-2005

AutomationDirect C-more EA9 HMI Cleartext Transmission

HighPUBLISHEDCNA: icscert
CNA base score7.5 CVSS v3.xCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N

02 Description

AutomationDirect C-more EA9 HMI Cleartext Transmission

03 Exploitation and scoring

Exploitation
Assessed, none found. CISA's assessment recorded neither public exploit code nor evidence of exploitation when it was made.
SSVC decision
  • ExploitationnoneCISA recorded no public exploit code and no evidence of exploitation.
  • AutomatableyesAn attacker can reliably automate reconnaissance through exploitation, so this scales.
  • Technical ImpactpartialSuccessful exploitation gives limited control of the vulnerable component.
CISA publishes the decision points, not a final SSVC decision. The decision also depends on mission and well-being impact, which is a property of your deployment rather than of the vulnerability.
EPSS probability
0.55% probability of exploitation activity in the next 30 days.
EPSS percentile
Equal to or higher than the score of 45.7% of scored records. A rank, not a probability.
NVD base score
7.5 (CVSS v3.x), scored by the NVD independently of the CNA.
NVD CVSS vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N
NVD analysis status
Modified. NVD last modified this record on 2026-06-17.
Red Hat severity
No Red Hat rating. Red Hat rates the CVEs that affect its products.

Exploit-prediction scores from FIRST. Independent scoring and analysis status from the NVD. Vendor severity from Red Hat. Exploitation assessment and catalog membership from CISA.

04 Metadata

Published
2022-08-31 15:33Z4 YR AGO
Last updated
2025-04-16 16:11Z1 YR AGO
Reserved
2022-06-06
Assigning CNA
icscert
Record state
PUBLISHED
Severity
High (CVSS 7.5)
CNA CVSS vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N
Weaknesses
  • CWE-319Cleartext Transmission of Sensitive InformationBase
Data version
5.1
Document digest
ac5fceca36b49e731dd831fb16b46e9b724b0a852dff06acd1946418aa2826d2

05 Affected products

VendorProductVersionsPlatforms
AutomationDirectC-more EA9EA9-T6CL to < 6.73, EA9-T6CL-R to < 6.73, EA9-T7CL to < 6.73, EA9-T7CL-R to < 6.73, EA9-T8CL to < 6.73, EA9-T10CL to < 6.73, EA9-T10WCL to < 6.73, EA9-T12CL to < 6.73, EA9-T15CL to < 6.73, EA9-RHMI to < 6.73, EA9-PGMSW to < 6.73—

06 References

07 Remediation

AutomationDirect recommends users upgrade to firmware Version 6.73 or later, which supports TLS security options for the webserver. While automation networks and systems have built-in password protection schemes, this is only one step in securing the affected systems. Automation control system networks must incorporate data protection and security measures at least as robust as a typical business computer system. AutomationDirect recommends users of PLCs, HMI products, and other SCADA system products perform independent network security analysis to determine the proper level of security required for the application. AutomationDirect has identified the following mitigations for instances where systems cannot be upgraded to Version 6.73 or later: The Webserver feature can be disabled on the HMI using the programming software. Place the HMI panel behind a VPN: Access to and from critical control system assets in the modern environment is usually LAN based, but still should be considered remote if the operator is traversing across different networks. virtual private networking (VPN) is often considered the best approach in securing trans-network communication.