CVE-2022-2003
AutomationDirect DirectLOGIC with Serial Communication Cleartext Transmission
02 Description
AutomationDirect DirectLOGIC with Serial Communication Cleartext Transmission
03 Exploitation and scoring
- Exploitation
- Assessed, none found. CISA's assessment recorded neither public exploit code nor evidence of exploitation when it was made.
- SSVC decision
- ExploitationnoneCISA recorded no public exploit code and no evidence of exploitation.
- AutomatablenoAt least one step from reconnaissance to exploitation cannot be reliably automated.
- Technical ImpacttotalSuccessful exploitation gives total control of the vulnerable component.
- EPSS probability
- 0.77% probability of exploitation activity in the next 30 days.
- EPSS percentile
- Equal to or higher than the score of 55.3% of scored records. A rank, not a probability.
- NVD base score
- 9.1 (CVSS v3.x), scored by the NVD independently of the CNA.
- NVD CVSS vector
- CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N
- NVD analysis status
- Modified. NVD last modified this record on 2026-06-17.
- Red Hat severity
- No Red Hat rating. Red Hat rates the CVEs that affect its products.
Exploit-prediction scores from FIRST. Independent scoring and analysis status from the NVD. Vendor severity from Red Hat. Exploitation assessment and catalog membership from CISA.
04 Metadata
- Published
- 2022-08-31 15:59Z4 YR AGO
- Last updated
- 2025-04-16 17:49Z1 YR AGO
- Reserved
- 2022-06-06
- Assigning CNA
- icscert
- Record state
- PUBLISHED
- Severity
- High (CVSS 7.7)
- CNA CVSS vector
- CVSS:3.1/AV:L/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N
- Weaknesses
- CWE-319Cleartext Transmission of Sensitive InformationBase
- Data version
- 5.1
- Document digest
- bcefda93b85b6ff5d42f41b6f33f856c582a97e570f1b44d5ff2fb3d169cee74
05 Affected products
06 References
07 Remediation
AutomationDirect recommends users upgrade to firmware Version 2.72 or later, which will no longer respond with the password when requested with the specially crafted message. Additional mitigation for brute force password access has also been added. Three incorrect password entries will result in a 3-hour lock out of password entry. Power cycle will allow subsequent password attempts. While automation networks and systems have built-in password protection schemes, this is only one step in securing the affected systems. Automation control system networks must incorporate data protection and security measures at least as robust as a typical business computer system. AutomationDirect recommends users of PLCs, HMI products, and other SCADA system products perform independent network security analysis to determine the proper level of security required for the application. AutomationDirect has identified the specific mitigation actions listed below: Secure physical access. Isolate and air gap networks when possible. Consider some of the AutomationDirect newer PLC families.