ICSA-22-090-05 Rockwell Automation Logix Controllers
ICSA-22-090-05 Rockwell Automation Logix Controllers
Exploit-prediction scores from FIRST. Independent scoring and analysis status from the NVD. Vendor severity from Red Hat. Exploitation assessment and catalog membership from CISA.
The following mitigations should be applied for ControlLogix 5560, ControlLogix 5570, ControlLogix 5580 series, GuardLogix 5570, GuardLogix 5580, GuardLogix 5380, CompactLogix, CompactLogix 5380 devices: Risk Mitigation A: Recompile and download user program code (i.e., acd). Put controller mode switch into Run position. If keeping controller mode switch in Run is impractical, use the following mitigation: Recompile and download user program code (i.e., acd). Monitor controller change log for any unexpected modifications or anomalous activity. Utilize the Controller Log feature. Utilize Change Detection in the Logix Designer Application. If available, use the functionality in FactoryTalk AssetCenter software to detect changes. Risk Mitigation B: Implement CIP Security to help prevent unauthorized connections when properly deployed. Supported controllers and communications modules include: ControlLogix 5580 processors using on-board EtherNet/IP port. GuardLogix 5580 processors using on-board EtherNet/IP port. ControlLogix 5580 processors operating in High Availability (HA) configurations using 1756-EN4TR ControlLogix 5560, ControlLogix 5570, ControlLogix 5580, GuardLogix 5570 and GuardLogix 5580 can use a 1756-EN4TR ControlLogix EtherNet/IP module. If using a 1756-EN2T, then replace with a 1756-EN4TR CompactLogix 5380 using on-board EtherNet/IP port. CompactLogix GuardLogix 5380 using on-board EtherNet/IP port. The following mitigations should be applied for 1768