synced 5 MIN AGO
01 Record

CVE-2021-42534

Trane Building Automation Controllers Cross-site Scripting

MediumPUBLISHEDCNA: icscert
CNA base score6.3 CVSS v3.xCVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:L

02 Description

Trane Building Automation Controllers Cross-site Scripting

03 Exploitation and scoring

Exploitation
Not assessed. CISA has not published an exploitation assessment for this record, and it is not in the KEV catalog. That is an absence of assessment, not a finding of no risk.
SSVC decision
Not assessed by CISA
EPSS probability
0.60% probability of exploitation activity in the next 30 days.
EPSS percentile
Equal to or higher than the score of 48.3% of scored records. A rank, not a probability.
NVD base score
6.1 (CVSS v3.x), scored by the NVD independently of the CNA.
NVD CVSS vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:N
NVD analysis status
Modified. NVD last modified this record on 2026-06-17.
Red Hat severity
No Red Hat rating. Red Hat rates the CVEs that affect its products.

Exploit-prediction scores from FIRST. Independent scoring and analysis status from the NVD. Vendor severity from Red Hat. Exploitation assessment and catalog membership from CISA.

04 Metadata

Published
2021-10-22 13:17Z5 YR AGO
Last updated
2024-09-16 23:52Z2 YR AGO
Reserved
2021-10-15
Assigning CNA
icscert
Record state
PUBLISHED
Severity
Medium (CVSS 6.3)
CNA CVSS vector
CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:L
Weaknesses
  • CWE-79Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting')Base
Data version
5.1
Document digest
2dfdd744e42a9ad50427fcd4c09f479837cefe4c3dfb044fc2ed300add58aa68

05 Affected products

VendorProductVersionsPlatforms
TraneTracer SCAll to 3.8—

06 References

07 Remediation

Trane has identified the following specific mitigations for the affected products: Users upgrade Tracer SC controllers running firmware v3.8 and prior, to firmware v4.4 SP7 or higher. Users should contact a regional Trane office to install updated firmware or request additional information and reference Trane service database number HUB-207592. Tracer SC is no longer actively developed, tested, or sold. Tracer SC will be considered end-of-life on December 31, 2022. Trane recommends users identify a migration plan to replace the Tracer SC controller with the Tracer SC+ controller, which can function as a drop-in replacement for Tracer SC, providing significant security upgrades.