synced 13 MIN AGO
01 Record

CVE-2021-33023

Advantech WebAccess

CriticalPUBLISHEDCNA: icscert
CNA base score9.8 CVSS v3.xCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

02 Description

Advantech WebAccess

03 Exploitation and scoring

Exploitation
Not assessed. CISA has not published an exploitation assessment for this record, and it is not in the KEV catalog. That is an absence of assessment, not a finding of no risk.
SSVC decision
Not assessed by CISA
EPSS probability
2.34% probability of exploitation activity in the next 30 days.
EPSS percentile
Equal to or higher than the score of 83.1% of scored records. A rank, not a probability.
NVD base score
9.8 (CVSS v3.x), scored by the NVD independently of the CNA.
NVD CVSS vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
NVD analysis status
Modified. NVD last modified this record on 2026-06-17.
Red Hat severity
No Red Hat rating. Red Hat rates the CVEs that affect its products.

Exploit-prediction scores from FIRST. Independent scoring and analysis status from the NVD. Vendor severity from Red Hat. Exploitation assessment and catalog membership from CISA.

04 Metadata

Published
2021-10-18 12:41Z5 YR AGO
Last updated
2024-09-17 03:49Z2 YR AGO
Reserved
2021-05-13
Assigning CNA
icscert
Record state
PUBLISHED
Severity
Critical (CVSS 9.8)
CNA CVSS vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Weaknesses
  • CWE-122Heap-based Buffer OverflowVariant
  • CWE-787Out-of-bounds WriteBase
Data version
5.1
Document digest
39d92ef3711b85c981823988c020d15a529a718718fddf82de3e743f425e4599

05 Affected products

VendorProductVersionsPlatforms
AdvantechWebAccessAll to 9.02—

06 References

07 Remediation

In order to address the heap-based buffer overflow vulnerability, Advantech recommends users directly add the remote access code to avoid being attacked by unknown requests. This is the remote access code established during installation of the Advantech WebAccess SCADA software (SCADA node, project node, or OPC Service) on the OPC Server computer. The access code you enter here must match the remote access code established during installation on the OPC Server. This prevents unauthorized users from accessing the OPC Server data using the Advantech WebAccess SCADA OPC Service. If you have forgotten the remote access code using during software installation on the OPC Server node, you have two options: Re-install the Advantech WebAccess SCADA software on the OPC Server node to change it and edit it to match in your database. Edit the BWSERVER.INI file on the OPC Server node and edit it to match in your database using UPDATE.