synced 8 MIN AGO
01 Record

CVE-2019-10952

Rockwell Automation CompactLogix 5370 Uncontrolled Resource Consumption

UnratedPUBLISHEDCNA: icscert
CNA base scoreUnratedNo CNA CVSS vector

02 Description

Rockwell Automation CompactLogix 5370 Uncontrolled Resource Consumption

03 Exploitation and scoring

Exploitation
Not assessed. CISA has not published an exploitation assessment for this record, and it is not in the KEV catalog. That is an absence of assessment, not a finding of no risk.
SSVC decision
Not assessed by CISA
EPSS probability
9.99% probability of exploitation activity in the next 30 days.
EPSS percentile
Equal to or higher than the score of 95.1% of scored records. A rank, not a probability.
NVD base score
9.8 (CVSS v3.x), scored by the NVD independently of the CNA.
NVD CVSS vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
NVD analysis status
Modified. NVD last modified this record on 2026-06-17.
Red Hat severity
No Red Hat rating. Red Hat rates the CVEs that affect its products.

Exploit-prediction scores from FIRST. Independent scoring and analysis status from the NVD. Vendor severity from Red Hat. Exploitation assessment and catalog membership from CISA.

04 Metadata

Published
2019-05-01 19:02Z7 YR AGO
Last updated
2024-08-04 22:40Z2 YR AGO
Reserved
2019-04-08
Assigning CNA
icscert
Record state
PUBLISHED
Severity
Not rated by the issuing CNA
CNA CVSS vector
Not published by the issuing CNA
Weaknesses
  • CWE-400Uncontrolled Resource ConsumptionClass
  • CWE-787Out-of-bounds WriteBase
Data version
5.1
Document digest
5e148661045e69a06ec6e514373f8cd5562fab51848d0a78a3b890c0e6be5952

05 Affected products

VendorProductVersionsPlatforms
Rockwell AutomationCompactLogix 5370 L1 controllers0 to < 20 - 30—
Rockwell AutomationCompactLogix 5370 L2 controllers0 to < 20 - 30—
Rockwell AutomationCompactLogix 5370 L3 controllers0 to < 20 - 30—
Rockwell AutomationCompact GuardLogix 5370 controllers0 to < 20 - 30—
Rockwell AutomationArmor Compact GuardLogix 5370 controllers0 to < 20 - 30—

06 References

07 Remediation

Rockwell Automation strongly encourages users to apply the latest available version of firmware to keep up to date with the latest features, anomaly fixes, and security improvements. Update firmware to version FRN 31.011 that mitigates the associated risk. Rockwell Automation also recommends the following: https://compatibility.rockwellautomation.com/Pages/MultiProductDownload.aspx * For EtherNet/IP-based vulnerabilities (ID 1-14), block all traffic to and from outside the Manufacturing Zone by blocking or restricting access to Port 2222/TCP/UDP and Port 44818/TCP/UDP using proper network infrastructure controls, such as firewalls, UTM devices, or other security appliances. For more information on TCP/UDP ports used by Rockwell Automation Products, see Knowledgebase Article ID 898270 https://rockwellautomation.custhelp.com/app/answers/detail/a_id/898270/page/1 (login required). * Stratix users can use Device Manager or Studio 5000 Logix Designer to configure access control lists (ACL) to block/restrict ports. See section “Access Control Lists” in Stratix Managed Switches User Manual, publication 1783-UM007 http://literature.rockwellautomation.com/idc/groups/literature/documents/um/1783-um007_-en-p.pdf , for detailed instructions. * For web-based vulnerabilities (ID 15-17), block all traffic from outside the Manufacturing Zone by blocking or restricting access to Port 80/443/TCP. * Stratix users can use Device Manager or Studio 5000 Logix Designer to configure ACL’s to